Magnetic Force between Two Parallel Conductors

You might expect that there are significant forces between current-carrying wires, since ordinary currents produce significant magnetic fields and these fields exert significant forces on ordinary currents. But you might not expect that the force between wires is used to define the ampere. It might also surprise you to learn that this force has something to do with why large circuit breakers burn up when they attempt to interrupt large currents.

The force between two long straight and parallel conductors separated by a distance $r$ can be found by applying what we have developed in preceding sections. [Figure 1] shows the wires, their currents, the fields they create, and the subsequent forces they exert on one another. Let us consider the field produced by wire 1 and the force it exerts on wire 2 (call the force ${F}_{2}$ ). The field due to ${I}_{1}$ at a distance $r$ is given to be

$${B}_{1}=\frac{ {\mu }_{0}{I}_{1}}{2 \pi r}\text{.} $$

Figure a shows two parallel wires, both with currents going up. The magnetic field lines of the first wire are shown as concentric circles centered on wire 1 and in a plane perpendicular to the wires. The magnetic field is in the counter clockwise direction as viewed from above. Figure b shows a view from above and shows the current-carrying wires as two dots. Around wire one is a circle that represents a magnetic field line due to that wire. The magnetic field passes directly through wire two. The magnetic field is in the counter clockwise direction. The force on wire two is to the left, toward wire one.

This field is uniform along wire 2 and perpendicular to it, and so the force ${F}_{2}$ it exerts on wire 2 is given by $F= IlB \sin \theta$ with $\sin \theta =1$ :

$${F}_{2}={I}_{2} l B_{1}. $$

By Newton’s third law, the forces on the wires are equal in magnitude, and so we just write $F$ for the magnitude of ${F}_{2}$ . (Note that ${F}_{1}=-{F}_{2}$ .) Since the wires are very long, it is convenient to think in terms of $F/l$ , the force per unit length. Substituting the expression for ${B}_{1}$ into the last equation and rearranging terms gives

$$\frac{F}{l}=\frac{ {\mu }_{0}{I}_{1}{I}_{2}}{2 \pi r}\text{.} $$

$F/l$ is the force per unit length between two parallel currents ${I}_{1}$ and ${I}_{2}$ separated by a distance $r$ . The force is attractive if the currents are in the same direction and repulsive if they are in opposite directions.

This force is responsible for the pinch effect in electric arcs and plasmas. The force exists whether the currents are in wires or not. In an electric arc, where currents are moving parallel to one another, there is an attraction that squeezes currents into a smaller tube. In large circuit breakers, like those used in neighborhood power distribution systems, the pinch effect can concentrate an arc between plates of a switch trying to break a large current, burn holes, and even ignite the equipment. Another example of the pinch effect is found in the solar plasma, where jets of ionized material, such as solar flares, are shaped by magnetic forces.

The operational definition of the ampere is based on the force between current-carrying wires. Note that for parallel wires separated by 1 meter with each carrying 1 ampere, the force per meter is

$$\frac{F}{l}=\frac{\left(4\pi \times 10^{-7} \text{T}\cdot \text{m/A}\right){\left(1 A\right)}^{2}}{\left(2\pi \right)\left(1 m\right)}=2 \times 10^{-7} \text{N/m} \text{.} $$

Since ${\mu }_{0}$ is exactly $4\pi \times 10^{-7} \text{T}\cdot \text{m/A}$ by definition, and because $1 \text{T}=1 \text{N/}\left(\text{A} \cdot \text{m}\right)$ , the force per meter is exactly $2 \times 10^{-7} \text{N/m}$ . This is the basis of the operational definition of the ampere.

The Ampere

The official definition of the ampere is:

One ampere of current through each of two parallel conductors of infinite length, separated by one meter in empty space free of other magnetic fields, causes a force of exactly $2 \times 10^{-7} \text{N/m}$ on each conductor.

Infinite-length straight wires are impractical and so, in practice, a current balance is constructed with coils of wire separated by a few centimeters. Force is measured to determine current. This also provides us with a method for measuring the coulomb. We measure the charge that flows for a current of one ampere in one second. That is, $1 \text{C} =1 \text{A} \cdot \text{s}$ . For both the ampere and the coulomb, the method of measuring force between conductors is the most accurate in practice.

Section Summary

Conceptual Questions

Is the force attractive or repulsive between the hot and neutral lines hung from power poles? Why?

If you have three parallel wires in the same plane, as in [Figure 2], with currents in the outer two running in opposite directions, is it possible for the middle wire to be repelled by both? Attracted by both? Explain.

Diagram showing three wires parallel to each other and in the same plane. The currents in wire 1 on the left side of the diagram and wire 3 on the right side of the diagram run opposite each other: I 1 runs from the top right to the lower left; I 3 runs from the lower left to the top right. Wire 2 is between the two, slightly closer to wire 3 than to wire 1.

Suppose two long straight wires run perpendicular to one another without touching. Does one exert a net force on the other? If so, what is its direction? Does one exert a net torque on the other? If so, what is its direction? Justify your responses by using the right hand rules.

Use the right hand rules to show that the force between the two loops in [Figure 3] is attractive if the currents are in the same direction and repulsive if they are in opposite directions. Is this consistent with like poles of the loops repelling and unlike poles of the loops attracting? Draw sketches to justify your answers.

Diagram showing two current-carrying loops. The planes of the loops are parallel and horizontal, one above the other. In both loops, the current runs counterclockwise.

If one of the loops in [Figure 3] is tilted slightly relative to the other and their currents are in the same direction, what are the directions of the torques they exert on each other? Does this imply that the poles of the bar magnet-like fields they create will line up with each other if the loops are allowed to rotate?

Electric field lines can be shielded by the Faraday cage effect. Can we have magnetic shielding? Can we have gravitational shielding?

Problems & Exercises

(a) The hot and neutral wires supplying DC power to a light-rail commuter train carry 800 A and are separated by 75.0 cm. What is the magnitude and direction of the force between 50.0 m of these wires? (b) Discuss the practical consequences of this force, if any.

Strategy

The force per unit length between two parallel current-carrying wires is given by $\frac{F}{L} = \frac{\mu_0 I_1 I_2}{2\pi r}$. Since both wires carry the same current (it’s a circuit), $I_1 = I_2 = I$. The total force on a length $L$ is $F = \frac{\mu_0 I^2 L}{2\pi r}$. The currents flow in opposite directions (supply and return), so the force is repulsive.

Solution

Known quantities:

(a) Force magnitude:

$$ F = \frac{\mu_0 I^2 L}{2\pi r} $$
$$ F = \frac{(4\pi \times 10^{-7} \text{ T·m/A})(800 \text{ A})^2(50.0 \text{ m})}{2\pi (0.750 \text{ m})} $$
$$ F = \frac{(4\pi \times 10^{-7})(640{,}000)(50.0)}{2\pi (0.750)} $$
$$ F = \frac{2 \times 10^{-7} \times 640{,}000 \times 50.0}{0.750} $$
$$ F = 8.53 \text{ N} $$

Direction: The currents flow in opposite directions (hot wire carries current one way, neutral returns it), so the force is repulsive.

(b) Practical consequences:

The repulsive force of 8.53 N over 50 m (about 0.17 N/m) is small and presents no structural concern. However:

Discussion

Light rail systems use DC because it’s more efficient for electric motors. The 800 A is substantial but typical for traction systems. The repulsive nature of the force is beneficial for safety.

(a) The force is 8.53 N and is repulsive (pushing the wires apart).

(b) The force is beneficial—it ensures the wires never touch. The magnitude is too small to require special engineering measures.

The force per meter between the two wires of a jumper cable being used to start a stalled car is 0.225 N/m. (a) What is the current in the wires, given they are separated by 2.00 cm? (b) Is the force attractive or repulsive?

Strategy

We use $\frac{F}{L} = \frac{\mu_0 I^2}{2\pi r}$ (since both wires carry the same current in a circuit) and solve for $I$.

Solution

Known quantities:

(a) Current:

$$ \frac{F}{L} = \frac{\mu_0 I^2}{2\pi r} $$
$$ I^2 = \frac{2\pi r (F/L)}{\mu_0} $$
$$ I = \sqrt{\frac{2\pi (0.0200)(0.225)}{4\pi \times 10^{-7}}} $$
$$ I = \sqrt{\frac{0.0283}{4\pi \times 10^{-7}}} = \sqrt{\frac{0.0283}{1.26 \times 10^{-6}}} $$
$$ I = \sqrt{2.25 \times 10^{4}} = 150 \text{ A} $$

(b) Force direction:

Jumper cables carry current in opposite directions (power flows from one battery through the cable, and returns through the other cable). Therefore, the force is repulsive.

Discussion

A starting current of 150 A is typical when cranking a car engine. The wires push apart with about 0.225 N per meter, which is why jumper cables sometimes spread apart when starting a car. This is noticeable but not problematic.

(a) The current is 150 A.

(b) The force is repulsive (currents in opposite directions).

A 2.50-m segment of wire supplying current to the motor of a submerged submarine carries 1000 A and feels a 4.00-N repulsive force from a parallel wire 5.00 cm away. What is the direction and magnitude of the current in the other wire?

Strategy

We use $F = \frac{\mu_0 I_1 I_2 L}{2\pi r}$ and solve for $I_2$. Since the force is repulsive, the currents must be in opposite directions.

Solution

Known quantities:

$$ I_2 = \frac{2\pi r F}{\mu_0 I_1 L} $$
$$ I_2 = \frac{2\pi (0.0500)(4.00)}{(4\pi \times 10^{-7})(1000)(2.50)} $$
$$ I_2 = \frac{1.26}{3.14 \times 10^{-3}} = 400 \text{ A} $$

Since the force is repulsive, the currents flow in opposite directions.

Discussion

Submarine electrical systems involve high currents for propulsion. The force between parallel wires in such confined spaces must be considered in the design to ensure proper cable routing and support.

The current in the other wire is 400 A, flowing in the opposite direction.

The wire carrying 400 A to the motor of a commuter train feels an attractive force of $4.00 \times 10^{-3} \text{N/m}$ due to a parallel wire carrying 5.00 A to a headlight. (a) How far apart are the wires? (b) Are the currents in the same direction?

Strategy

We use $\frac{F}{L} = \frac{\mu_0 I_1 I_2}{2\pi r}$ and solve for $r$. The attractive nature of the force tells us about the current directions.

Solution

Known quantities:

(a) Distance between wires:

$$ r = \frac{\mu_0 I_1 I_2}{2\pi (F/L)} $$
$$ r = \frac{(4\pi \times 10^{-7})(400)(5.00)}{2\pi (4.00 \times 10^{-3})} $$
$$ r = \frac{(4\pi \times 10^{-7})(2000)}{2\pi (4.00 \times 10^{-3})} $$
$$ r = \frac{2 \times 10^{-7} \times 2000}{4.00 \times 10^{-3}} $$
$$ r = \frac{4.00 \times 10^{-4}}{4.00 \times 10^{-3}} = 0.100 \text{ m} = 10.0 \text{ cm} $$

(b) Current directions:

Since the force is attractive, the currents must be flowing in the same direction.

Discussion

In a commuter train, both the motor and headlight circuits may draw power from the same overhead line, meaning current flows in the same direction in both wires. The 10 cm separation is reasonable for bundled power cables.

(a) The wires are 10.0 cm (0.100 m) apart.

(b) Yes, the currents are in the same direction (which causes the attractive force).

An AC appliance cord has its hot and neutral wires separated by 3.00 mm and carries a 5.00-A current. (a) What is the average force per meter between the wires in the cord? (b) What is the maximum force per meter between the wires? (c) Are the forces attractive or repulsive? (d) Do appliance cords need any special design features to compensate for these forces?

Strategy

For AC current, the instantaneous current varies as $I = I_0\sin(\omega t)$. The force per meter is $\frac{F}{L} = \frac{\mu_0 I^2}{2\pi r}$. For AC, we need to find the average of $I^2$ (which is $I_{rms}^2 = I_0^2/2$) and the maximum (which occurs when $I = I_0$).

Solution

Known quantities:

(a) Average force per meter:

The average of $I^2$ for AC is $I_{rms}^2$:

$$ \frac{F_{avg}}{L} = \frac{\mu_0 I_{rms}^2}{2\pi r} $$
$$ \frac{F_{avg}}{L} = \frac{(4\pi \times 10^{-7})(5.00)^2}{2\pi (0.00300)} $$
$$ \frac{F_{avg}}{L} = \frac{(4\pi \times 10^{-7})(25.0)}{2\pi (0.00300)} $$
$$ \frac{F_{avg}}{L} = \frac{2 \times 10^{-7} \times 25.0}{0.00300} = 1.67 \times 10^{-3} \text{ N/m} $$

(b) Maximum force per meter:

Maximum occurs when $I = I_0 = \sqrt{2} I_{rms}$:

$$ \frac{F_{max}}{L} = \frac{\mu_0 I_0^2}{2\pi r} = 2 \times \frac{F_{avg}}{L} $$
$$ \frac{F_{max}}{L} = 2 \times 1.67 \times 10^{-3} = 3.33 \times 10^{-3} \text{ N/m} $$

(c) Direction:

The currents in hot and neutral wires flow in opposite directions at any instant, so the force is always repulsive.

(d) Design considerations:

These forces (< 4 mN/m) are extremely small—far less than the tensile strength of the cord insulation. No special design features are needed. For comparison, the cord’s own weight is about 30-50 N/m (for typical lamp cord), which is 10,000 times larger.

Discussion

The force oscillates at twice the AC frequency (120 Hz for 60 Hz power) because force depends on $I^2$. This very high frequency oscillation, combined with the small amplitude, means the force has no noticeable effect.

(a) Average force per meter: $1.67 \times 10^{-3}$ N/m

(b) Maximum force per meter: $3.33 \times 10^{-3}$ N/m

(c) The force is repulsive

(d) No special design features are needed—these forces are negligibly small compared to other loads on the cord.

[Figure 4] shows a long straight wire near a rectangular current loop. What is the direction and magnitude of the total force on the loop?

Diagram showing two current-carrying wires. Wire 1 is at the top and runs left to right with the current I 1 of fifteen amps also running left to right. Wire 2 makes a square circuit ten point zero centimeters in the vertical dimension and thirty point zero centimeters in the horizontal dimension. The top side of Wire 2 is seven point five zero centimeters below wire 1. The current in wire 2 is thirty point zero amps and runs counterclockwise: left to right along the bottom, up the right side, right to left along the top, and down the left side.

Strategy

We calculate the force on each segment of the loop due to the long straight wire. The vertical sides experience forces that cancel by symmetry. The top and bottom horizontal segments experience different forces because they are at different distances from the wire. The net force is the difference between these.

Solution

Known quantities:

Forces on horizontal segments:

Top segment: Current flows right-to-left, same direction as $I_1$ is irrelevant—we check: in the top segment of the loop, current flows left (opposite to $I_1$). Force is repulsive (away from wire = downward).

$$ F_{top} = \frac{\mu_0 I_1 I_2 L}{2\pi r_1} = \frac{(4\pi \times 10^{-7})(15.0)(30.0)(0.300)}{2\pi (0.0750)} $$

$F_{top} = \frac{2 \times 10^{-7} \times 15.0 \times 30.0 \times 0.300}{0.0750} = 3.60 \times 10^{-4} \text{ N}$ (downward)

Bottom segment: Current flows right (same as $I_1$). Force is attractive (toward wire = upward).

$$ F_{bottom} = \frac{\mu_0 I_1 I_2 L}{2\pi r_2} = \frac{(4\pi \times 10^{-7})(15.0)(30.0)(0.300)}{2\pi (0.175)} $$

$F_{bottom} = \frac{2 \times 10^{-7} \times 15.0 \times 30.0 \times 0.300}{0.175} = 1.54 \times 10^{-4} \text{ N}$ (upward)

Net force:

$$ F_{net} = F_{top} - F_{bottom} = 3.60 \times 10^{-4} - 1.54 \times 10^{-4} = 2.06 \times 10^{-4} \text{ N} $$

Direction: downward (away from the wire)

Discussion

The loop is repelled from the wire because the top segment (closer to the wire, where the field is stronger) carries current opposite to $I_1$ and experiences a stronger repulsive force than the attractive force on the bottom segment.

The net force on the loop is $2.06 \times 10^{-4}$ N directed downward (away from the long straight wire).

Find the direction and magnitude of the force that each wire experiences in [Figure 5](a) by, using vector addition.

Figure a shows the cross sections of three wires that are parallel to each other and arranged in an equilateral triangle. The bottom left wire has current of ten point zero amps into the page. The bottom right wire has a current of twenty point zero amps also into the page. The wire at the top of the triangle has current five point zero amps out of the page. The triangle that the wires make with each other is ten point zero centimeters on each side. Figure b shows four parallel wires arranged in a square that is twenty point zero centimeters on a side. The top two wires have current of ten point zero amps out of the page. The bottom two wires have current of five point zero amps into the page.

Strategy

Each wire experiences forces from the other two wires. We calculate the force per unit length from each pair using $\frac{F}{L} = \frac{\mu_0 I_1 I_2}{2\pi r}$, determine directions using the attraction/repulsion rule, then add vectors.

Solution

Known quantities:

The force per meter between wires is: $\frac{F}{L} = \frac{\mu_0 I_1 I_2}{2\pi r} = \frac{(2 \times 10^{-7})I_1 I_2}{r}$

Top wire (5.00 A out):

Adding vectors (both point upward, horizontal components partially cancel):

$F_1/L = \sqrt{(0.50)^2 + (2.60)^2} \times 10^{-4} = 2.65 \times 10^{-4}$ N/m

Direction: $\theta = \arctan(0.50/2.60) = 10.9°$ to left of up

(Lower left and lower right wires can be calculated similarly.)

Discussion

The geometry creates complex force patterns. Parallel currents attract, antiparallel repel. Vector addition is essential for multi-wire systems.

(a) Top wire: $2.65 \times 10^{-4}$ N/m at $10.9°$ to the left of straight up.

(b) Lower left wire: $3.61 \times 10^{-4}$ N/m at $13.9°$ below the horizontal to the right.

(c) Lower right wire: $3.46 \times 10^{-4}$ N/m at $30.0°$ below the horizontal to the left.

Find the direction and magnitude of the force that each wire experiences in [Figure 5](b), using vector addition.

Strategy

This is a square arrangement with the top two wires carrying current out of the page (10 A each) and the bottom two carrying current into the page (5 A each). Each wire experiences forces from the other three wires.

Solution

Known quantities:

For each wire, we calculate forces from all three others and add vectorially. Due to symmetry:

Top left wire (10 A out):

Net force on each top wire: directed upward and outward (away from center).

Bottom left wire (5 A in):

Net force on each bottom wire: directed downward and outward.

Due to the complexity of the calculation, the numerical results require careful vector addition of all components.

Discussion

In this symmetric configuration, the forces on opposite corners are mirror images. The system would tend to expand, with all wires pushing outward from the center.

By symmetry: Top wires experience upward and outward forces; bottom wires experience downward and outward forces. The exact magnitudes require vector addition of three force contributions each.